3.18 Main Menu - Time-based Functions - Group 23
3.18.1 23-0* Timed Actions
Use
Timed Actions
for actions needing to be performed on a daily or weekly basis, e.g. different references for working hours / non-working hours. Up
to 10 Timed Actions can be programmed in the frequency converter. The Timed Action number is selected from the list when entering parameter group
23-0* from the LCP. par.23-00
then refer to the selected Timed Action number. Each Timed Action is divided into an
ON time and an OFF time, in which two different actions may be performed.
The actions programmed in Timed Actions are merged with corresponding actions from digital inputs, control work via bus and Smart Logic Controller,
according to merge rules set up in 8-5*, Digital/Bus.
NB!
The clock (parameter group 0-7*) must be correctly programmed for Timed Actions to function correctly.
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date and time is included.
NB!
The PC-based Configuration Tool MCT 10 comprise a special guide for easy programming of Timed Actions.
23-00 ON Time
Array [10]
Range:
Function:
0 N/A*
[0 - 0 N/A]
Sets the ON time for the Timed Action.
NB!
The frequency converter has no back up of the clock function and the set date/
time will reset to default (2000-01-01 00:00) after a power down unless a Real
Time Clock module with back up is installed. In par.0-79
it is possible
to program for a Warning in case clock has not been set properly, e.g. after a
power down.
23-01 ON Action
Select the action during ON Time. See par. 13.52
SL Controller Action
for descriptions of the options.
Array [10]
[0] *
DISABLED
[1]
No action
[2]
Select setup 1
[3]
Select setup 2
[4]
Select setup 3
[5]
Select setup 4
[10]
Select preset ref. 0
[11]
Select preset ref. 1
ADAP-KOOL
®
Drive Programming Guide
3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
185
3