External stop signals activated by means of control signals or a serial bus will override a 'start' command via the LCP.
The following control signals will still be active when [Hand on] is activated:
•
[Hand on] - [Off] - [Auto on]
•
Reset
•
Coasting stop inverse
•
Reversing
•
Set-up select lsb - Set-up select msb
•
Stop command from serial communication
•
Quick stop
•
DC brake
[Off]
stops the connected motor. The key can be selected as
Enable
[1] or
Disable
If no external stop function is selected and the [Off] key is inactive the motor can be stopped by disconnecting the mains supply.
[Auto on]
enables the frequency converter to be controlled via the control terminals and/or serial communication. When a start signal is applied on the
control terminals and/or the bus, the frequency converter will start. The key can be selected as
Enable
[1] or
Disable
[0] via par.0-42
.
NB!
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the control keys [Hand on] [Auto on].
[Reset]
is used for resetting the frequency converter after an alarm (trip). It can be selected as
Enable
[1] or
Disable
[0] via par.0-43
.
2.1.3 Quick Transfer of Parameter Settings between Multiple Frequency Converters
Once the set-up of a frequency converter is complete, we recommend
that you store the data in the LCP or on a PC via MCT 10 Set-up Software
Tool.
Data storage in LCP:
1.
Go to par.0-50
2.
Press the [OK] key
3.
Select “All to LCP”
4.
Press the [OK] key
All parameter settings are now stored in the LCP indicated by the progress bar. When 100% is reached, press [OK].
2 How to Programme
ADAP-KOOL
®
Drive Programming Guide
22
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
2