5-68 Pulse Output Max Freq #X30/6
Range:
Function:
5000. Hz* [0 - 32000 Hz]
Select the maximum frequency on terminal X30/6 referring to the output variable in par.5-66
minal X30/6 Pulse Output Variable
. This parameter cannot be adjusted while the motor is running.
This parameter is active when option module MCB 101 is mounted in the frequency converter.
3.7.8 5-9*Bus Controlled
This parameter group selects digital and relay outputs via a fieldbus setting.
5-90 Digital & Relay Bus Control
Range:
Function:
0 N/A*
[0 - 2147483647 N/A]
This parameter holds the state of the digital outputs and relays that is controlled by bus.
A logical '1' indicates that the output is high or active.
A logical '0' indicates that the output is low or inactive.
Bit 0
CC Digital Output Terminal 27
Bit 1
CC Digital Output Terminal 29
Bit 2
GPIO Digital Output Terminal X 30/6
Bit 3
GPIO Digital Output Terminal X 30/7
Bit 4
CC Relay 1 output terminal
Bit 5
CC Relay 2 output terminal
Bit 6
Option B Relay 1 output terminal
Bit 7
Option B Relay 2 output terminal
Bit 8
Option B Relay 3 output terminal
Bit 9-15
Reserved for future terminals
Bit 16
Option C Relay 1 output terminal
Bit 17
Option C Relay 2 output terminal
Bit 18
Option C Relay 3 output terminal
Bit 19
Option C Relay 4 output terminal
Bit 20
Option C Relay 5 output terminal
Bit 21
Option C Relay 6 output terminal
Bit 22
Option C Relay 7 output terminal
Bit 23
Option C Relay 8 output terminal
Bit 24-31
Reserved for future terminals
5-93 Pulse Out #27 Bus Control
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Contains the frequency to apply to the digital output terminal 27, when it is configured as [Bus
Controlled].
5-94 Pulse Out #27 Timeout Preset
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Contains the frequency to apply to the digital output terminal 27, when it is configured as [Bus
Controlled Timeout] and timeout is detected.
5-95 Pulse Out #29 Bus Control
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Contains the frequency to apply to the digital output terminal 29, when it is configured as [Bus
Controlled].
5-96 Pulse Out #29 Timeout Preset
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Contains the frequency to apply to the digital output terminal 29, when it is configured as [Bus
Controlled Timeout] and timeout is detected
ADAP-KOOL
®
Drive Programming Guide
3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
83