22-42 Wake-up Speed [RPM]
Range:
Function:
0 RPM*
[par. 4-11 - par. 4-13 RPM]
To be used if par.0-02
has been set for RPM (parameter not visible if Hz selected).
Only to be used if par.1-00
is set for Open Loop and speed reference is applied
by an external controller.
Set the reference speed at which the Sleep Mode should be cancelled.
22-43 Wake-up Speed [Hz]
Range:
Function:
0 Hz*
[par. 4-12 - par. 4-14 Hz]
To be used if par.0-02
, has been set for Hz (parameter not visible if RPM selected).
Only to be used if par.1-00
, is set for Open Loop and speed reference is applied
by an external controller controlling the pressure.
Set the reference speed at which the Sleep Mode should be cancelled.
22-44 Wake-up Ref./FB Difference
Range:
Function:
10 %*
[0 - 100 %]
Only to be used if par.1-00
is set for Closed Loop and the integrated PI controller
is used for controlling the pressure.
Set the pressure drop allowed in percentage of set point for the pressure (Pset) before cancelling
the Sleep Mode.
NB!
If used in application where the integrated PI controller is set for inverse control (e.g. cooling tower applications) in par.20-71
will automatically be added.
22-45 Setpoint Boost
Range:
Function:
0 %*
[-100 - 100 %]
Only to be used if par.1-00
, is set for Closed Loop and the integrated PI con-
troller is used. In systems with e.g. constant pressure control, it is advantageous to increase the
system pressure before the motor is stopped. This will extend the time in which the motor is stopped
and help to avoid frequent start/stop.
Set the desired over pressure/temperature in percentage of set point for the pressure (Pset)/tem-
perature before entering the Sleep Mode.
If setting for 5%, the boost pressure will be Pset*1.05. The negative values can be used for e.g.
cooling tower control where a negative change is needed.
22-46 Maximum Boost Time
Range:
Function:
60 s*
[0 - 600 s]
Only to be used if par.1-00
is set for Closed Loop and the integrated PI controller
is used for controlling the pressure.
Set the maximum time for which boost mode will be allowed. If the set time is exceeded, Sleep
Mode will be entered, not waiting for the set boost pressure to be reached.
3.17.4 22-5* AP-5# End of Curve
The End of Curve conditions occur when a pump is yielding a too large volume to ensure the set pressure. This can occur if there is a leakage in the
distribution pipe system after the pump causing the pump to operate at the end of the pump characteristic, valid for the max. speed set in par.
4-13
or par.4-14
.
In case the feed back is 2.5% of the programmed value in par. CL-14
Maximum Reference/Feedb.
(or numerical value of par. CL-13
Minimum Reference/
Feedb.
whichever is highest) below the set point for the desired pressure for a set time (par.22-51
), and the pump is running with
max. speed set in par.4-13
, - the function selected in par.22-50
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
178
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark