1.1.9 Speed Up/Down
Terminals 29/32 = Speed up/down:.
Terminal 18 = par. 5-10
Terminal 18 Digital Input
Start [9] (de-
fault)
Terminal 27 = par. 5-12
Terminal 27 Digital Input
Freeze refer-
ence [19]
Terminal 29 = par. 5-13
Terminal 29 Digital Input
Speed up [21]
Terminal 32 = par. 5-14
Terminal 32 Digital Input
Speed down
[22]
Note: Terminal 29 only in FC x02 (x=series type).
1.1.10 Potentiometer Reference
Voltage reference via a potentiometer:
Reference Source 1 = [1]
Analog input 53
(default)
Terminal 53, Low Voltage = 0 Volt
Terminal 53, High Voltage = 10 Volt
Terminal 53, Low Ref./Feedback = 0 RPM
Terminal 53, High Ref./Feedback = 1500 RPM
Switch S201 = OFF (U)
ADAP-KOOL
®
Drive Programming Guide
1 Introduction
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
13
1