0-60 Main Menu Password
Range:
Function:
100 N/A*
[0 - 999 N/A]
Define the password for access to the Main Menu via the [Main Menu] key. If par.0-61
is set to
Full access
[0], this parameter will be ignored.
0-61 Access to Main Menu w/o Password
Option:
Function:
[0] *
Full access
Disables password defined in par.0-60
.
[1]
Read only
Prevent unauthorized editing of Main Menu parameters.
[2]
No access
Prevent unauthorized viewing and editing of Main Menu parameters.
If
Full access
[0] is selected then par.0-60
Access to Personal Menu w/o Pass-
will be ignored.
0-65 Personal Menu Password
Range:
Function:
200 N/A*
[0 - 999 N/A]
Define the password for access to the My Personal Menu via the [Quick Menu] key. If par.
0-66
Access to Personal Menu w/o Password
is set to
Full access
[0], this parameter will be ignored.
0-66 Access to Personal Menu w/o Password
Option:
Function:
[0] *
Full access
Disables password defined in par.0-65
[1]
Read only
Prevents unauthorized editing of My Personal Menu parameters.
[2]
No access
Prevents unauthorized viewing and editing of My Personal Menu parameters.
If par.0-61
Access to Main Menu w/o Password
is set to
Full access
[0], this parameter will be ignored.
3.2.9 Clock Settings, 0-7*
Set the time and date of the internal clock. The internal clock can be used for e.g. Timed Actions, energy log, Trend Analysis, date/time stamps on alarms,
Logged data and Preventive Maintenance.
It is possible to program the clock for Daylight Saving Time / summertime, weekly working days/non-working days including 20 exceptions (holidays
etc.). Although the clock settings can be set via the LCP, they can also be set along with timed actions and preventative maintenance functions using the
MCT10 software tool.
NB!
The frequency converter has no back up of the clock function and the set date/time will reset to default (2000-01-01 00:00) after a
power down unless a Real Time Clock module with back up is installed. If no module with back up is installed, it is recommended the
clock function is only used if the frequency converter is integrated into the BMS using serial communications, with the BMS maintaining
synchronization of control equipment clock times. In par.0-79
it is possible to program for a Warning in case clock has not
been set properly, e.g. after a power down.
NB!
If mounting an Analog I/O MCB 109 option card, a battery back-up of the date and time is included.
0-70 Set Date and Time
Range:
Function:
0 N/A*
[0 - 0 N/A]
Sets the date and time of the internal clock. The format to be used is set in par.0-71
ADAP-KOOL
®
Drive Programming Guide
3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
43
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...