[3]
Coast and reset inverse
Reset and coasting stop Inverted input (NC).
Leaves motor in free mode and resets the frequency converter. Logic ‘0’ => coasting stop and reset.
[5]
DC-brake inverse
Inverted input for DC braking (NC).
Stops motor by energizing it with a DC current for a certain time period. See par. 2-01 to par. 2-03.
The function is only active when the value in par. 2-02 is different from 0. Logic ’0’ => DC braking.
[6]
Stop inverse
Stop Inverted function. Generates a stop function when the selected terminal goes from logical level
‘1’ to ‘0’. The stop is performed according to the selected ramp time (par. 3-42, par. 3-52, par. 3-62,
par. 3-72).
NB!
When the frequency converter is at the torque limit and has received a stop
command, it may not stop by itself. To ensure that the frequency converter stops,
configure a digital output to
Torque limit & stop
[27] and connect this digital
output to a digital input that is configured as coast.
[7]
External Interlock
Same function as Coasting stop, inverse, but External Interlock generates the alarm message ’ex-
ternal fault’ on the display when the terminal which is programmed for Coast Inverse is logic ‘0’.
The alarm message will also be active via digital outputs and relay outputs, if programmed for
External Interlock. The alarm can be reset using a digital input or the [RESET] key if the cause for
the External Interlock has been removed. A delay can be programmed in par. 22-00, External In-
terlock Time. After applying a signal to the input, the reaction described above will be delayed with
the time set in par. 22-00.
[8]
Start
Select start for a start/stop command. Logic ‘1’ = start, logic ‘0’ = stop.
(Default Digital input 18)
[9]
Latched start
Motor starts, if a pulse is applied for min. 2 ms. Motor stops when Stop inverse is activated
[10]
Reversing
Changes direction of motor shaft rotation. Select Logic ‘1’ to reverse. The reversing signal only
changes the direction of rotation. It does not activate the start function. Select both directions in
par. 4-10
Motor Speed Direction
.
(Default Digital input 19).
[11]
Start reversing
Used for start/stop and for reversing on the same wire. Signals on start are not allowed at the same
time.
[14]
Jog
Used for activating jog speed. See par. 3-11.
(Default Digital input 29)
[15]
Preset reference on
Used for shifting between external reference and preset reference. It is assumed that
External/
preset
[1] has been selected in par. 3-04. Logic '0' = external reference active; logic '1' = one of
the eight preset references is active.
[16]
Preset ref bit 0
Enables a choice between one of the eight preset references according to the table below.
[17]
Preset ref bit 1
Enables a choice between one of the eight preset references according to the table below.
[18]
Preset ref bit 2
Enables a choice between one of the eight preset references according to the table below.
Preset ref. bit
2
1
0
Preset ref. 0
0
0
0
Preset ref. 1
0
0
1
Preset ref. 2
0
1
0
Preset ref. 3
0
1
1
Preset ref. 4
1
0
0
Preset ref. 5
1
0
1
Preset ref. 6
1
1
0
Preset ref. 7
1
1
1
[19]
Freeze ref
Freezes actual reference. The frozen reference is now the point of enable/condition for Speed up
and Speed down to be used. If Speed up/down is used, the speed change always follows ramp 2
(par. 3-51 and 3-52) in the range 0 - par. 3-03
Maximum Reference
.
[20]
Freeze output
Freezes actual motor frequency (Hz). The frozen motor frequency is now the point of enable/con-
dition for Speed up and Speed down to be used. If Speed up/down is used, the speed change always
follows ramp 2 (par. 3-51 and 3-52) in the range 0 - par. 1-23
Motor Frequency
.
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
70
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark