4-61 Bypass Speed From [Hz]
Array [4]
Range:
Function:
0 Hz*
[0.0 - par. 4-14 Hz]
Some systems call for avoiding certain output speeds due to resonance problems in the system.
Enter the lower limits of the speeds to be avoided.
4-62 Bypass Speed To [RPM]
Array [4]
Range:
Function:
0 RPM*
[0 - par. 4-13 RPM]
Some systems call for avoiding certain output speeds due to resonance problems in the system.
Enter the upper limits of the speeds to be avoided.
4-63 Bypass Speed To [Hz]
Array [4]
Range:
Function:
0 Hz*
[0.0 - par. 4-14 Hz]
Some systems call for avoiding certain output speeds due to resonance problems in the system.
Enter the upper limits of the speeds to be avoided.
3.7 Main Menu - Digital In/Out - Group 5
3.7.1 5-** Digital In/Out
Parameter group for configuring the digital input and output.
3.7.2 5-0* Digital I/O Mode
Parameters for configuring the input and output using NPN and PNP.
5-00 Digital I/O Mode
Option:
Function:
Digital inputs and programmed digital outputs are pre-programmable for operation either in PNP or
NPN systems.
[0] *
PNP - Active at 24V
Action on positive directional pulses (0). PNP systems are pulled down to GND.
[1]
NPN - Active at 0V
Action on negative directional pulses (1). NPN systems are pulled up to + 24 V, internally in the
frequency converter.
NB!
This parameter cannot be adjusted while the motor is running.
5-01 Terminal 27 Mode
Option:
Function:
[0] *
Input
Defines terminal 27 as a digital input.
[1]
Output
Defines terminal 27 as a digital output.
Please not that this parameter cannot be adjusted while the motor is
running.
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
68
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...