
The difference between the Reference Power at fixed speed and the Actual Power yielded with speed control represent the actual saving.
As value for the fixed speed case, the rated motor size (kW) is multiplied with a factor (set in %) representing the power produced at fixed speed. The
difference between this reference power and the actual power is accumulated and stored. The difference in energy can be read in par. 23-83,
Energy
Savings
.
The accumulated value for the difference in power consumption is multiplied with the energy cost in local currency and the investment is subtracted. This
calculation for Cost Savings can also be read in par. 23-84,
Cost Savings
.
Cost
Savings
=
{
∑
t
=0
t
(
Rated
Motor
Power
∗
Power
Reference
Factor
)
−
Actual
Power
Consumption
×
Energy
Cost
}
−
Investment
Cost
Break even (payback) occurs when the value read in the parameter turns from negative to positive.
It is not possible to reset the Energy Savings counter, but the counter can be stopped any time by setting par. 28-80,
Power Reference Factor
, to 0.
Parameter overview:
Parameter for settings
Parameters for readout
Rated Motor Power
Par. 1-20
Energy Savings
Par. 23-83
Power Reference Factor in %
Par. 23-80
Actual Power
Par. 16-10/11
Energy Cost per kWh
Par. 23-81
Cost Savings
Par. 23-84
Investment
Par. 23-82
23-80 Power Reference Factor
Range:
Function:
100 %*
[0 - 100 %]
Set the percentage of the rated motor size (set in par.1-20
) which is supposed to represent the average power yielded at the time running with
fixed speed (before upgrade with variable speed control).
Must be set to a value different from zero to start counting.
23-81 Energy Cost
Range:
Function:
1.00 N/A* [0.00 - 999999.99 N/A]
Set the actual cost for a kWh in local currency. If the energy cost is changed later on it will impact
the calculation for the entire period!
23-82 Investment
Range:
Function:
0 N/A*
[0 - 999999999 N/A]
Set the value of the investment spent on upgrading the plant with speed control, in same currency
as used in par.23-81
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
198
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...