26-31 Terminal X42/5 High Voltage
Range:
Function:
10.00 V*
[par. 6-30 - 10.00 V]
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par.26-35
Term. X42/5 High Ref./Feedb. Value
.
26-34 Term. X42/5 Low Ref./Feedb. Value
Range:
Function:
0.000 N/A* [-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the low voltage value set in par.
26-30
26-35 Term. X42/5 High Ref./Feedb. Value
Range:
Function:
100.000 N/
A*
[-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the high voltage value set in par.
26-21
26-36 Term. X42/5 Filter Time Constant
Range:
Function:
0.001 s*
[0.001 - 10.000 s]
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
noise in terminal X42/5. A high time constant value improves dampening but also increases the time
delay through the filter. This parameter cannot be adjusted while the motor is running.
26-37 Term. X42/5 Live Zero
Option:
Function:
This parameter makes it possible to enable the Live Zero monitoring. E.g. where the analog input
is a part of the frequency converter control, rather than being used as part of a decentral I/O system,
such as a Building Management System.
[0]
Disabled
[1] *
Enabled
26-40 Terminal X42/7 Output
Option:
Function:
Set the function of terminal X42/7 as an analog voltage output.
[0] *
No operation
[100]
Output frequency
: 0 - 100 Hz, (0-20 mA)
[101]
Reference
: Minimum reference - Maximum reference, (0-20 mA)
[102]
Feedback
: -200% to +200% of par. CL-14
Maximum Reference/Feedb.
, (0-20 mA)
[103]
Motor current
[104]
Torque rel to limit
: 0 - Torque limit (par.4-16
), (0-20 mA)
[105]
Torq relate to rated
: 0 - Motor rated torque, (0-20 mA)
[106]
Power
: 0 - Motor rated power, (0-20 mA)
[107]
Speed
: 0 - Speed High Limit (par.4-13
), (0-20 mA)
[108]
Torque
[109]
Max Out Freq
[113]
Ext. Closed Loop 1
: 0 - 100%, (0-20 mA)
[114]
Ext. Closed Loop 2
: 0 - 100%, (0-20 mA)
[115]
Ext. Closed Loop 3
: 0 - 100%, (0-20 mA)
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
214
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...