3.9.3 8-1* Ctrl. Word Settings
Parameters for configuring the option control word profile.
8-10 Control Profile
Option:
Function:
Select the interpretation of the control and status words corresponding to the installed fieldbus.
Only the selections valid for the fieldbus installed in slot A will be visible in the LCP display.
[0] *
FC profile
8-13 Configurable Status Word STW
Option:
Function:
This parameter enables configuration of bits 12 – 15 in the status word.
[0]
No function
[1] *
Profile Default
Function corresponds to the profile default selected in par.8-10
3.9.4 8-3* FC Port Settings
Parameters for configuring the FC Port.
8-30 Protocol
Protocol selection for the integrated FC (standard) Port (RS485) on the control card.
Parameter group 8-7* is only visible when FC Option [9] is chosen.
Option:
Function:
[0] *
FC
Communication according to the FC Protocol as described in the
AKD102 Design Guide, chapter:
RS-485 Installation and Set-up
.
[1]
FC MC
Same as
FC
[0] but to be used when downloading SW to the frequency converter or uploading dll
file (covering information regarding parameters available in the frequency converter and their inter-
dependencies) to Motion Control Tool MCT10.
[2]
Modbus RTU
Communication according to the Modbus RTU protocol as described in the
AKD102 Design Guide,
chapter: RS-485 Installation and Set-up
.
[3]
Metasys N2
Communication protocol. The N2 software protocol is designed to be general in nature in order to
accommodate the unique properties each device may have. Please see separate manual
VLT
®
HVAC
Drive Metasys, MG.11.Gx.yy
.
[9]
FC option
To be used when a gateway is connected to the integrated RS-485 port, e.g. the BACnet gateway.
Following changes will take place:
-Address for the FC port will be set to 1 and
par. 8-31 Address
, is now used to set the address for
the gateway on the network, e.g. BACnet.
Please see separate manual
VLT
®
HVAC Drive BACnet, MG.11.Dx.yy
.
-Baud rate for the FC port will be set to a fixed value (115.200 Baud) and
par. 8-32 Baud Rate
, is
now used to set the baud rate for the network port (e.g. BACnet) on the gateway.
NB!
Further details can be found in the BACnet and Metasys manuals.
8-31 Address
Range:
Function:
1. N/A*
[1. - 126. N/A]
Enter the address for the FC (standard) port.
Valid range: 1 - 126.
ADAP-KOOL
®
Drive Programming Guide
3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
97
3