15-21 Historic Log: Value
Array [50]
Range:
Function:
0 N/A*
[0 - 2147483647 N/A]
View the value of the logged event. Interpret the event values according to this table:
Digtal input
Decimal value. See par.16-60
for description
after converting to binary value.
Digital output (not monitored in
this SW release)
Decimal value. See par. 16-66
Digital Output [bin]
for de-
scription after converting to binary value.
Warning word
Decimal value. See par. 16-92
Warning Word
for descrip-
tion.
Alarm word
Decimal value. See par. 16-90
Alarm Word
for description.
Status word
Decimal value. See par.16-03
for description
after converting to binary value.
Control word
Decimal value. See par.16-00
for description.
Extended status word
Decimal value. See par. 16-94
Ext. Status Word
for de-
scription.
15-22 Historic Log: Time
Array [50]
Range:
Function:
0 ms*
[0 - 2147483647 ms]
View the time at which the logged event occurred. Time is measured in ms since frequency converter
start. The max. value corresponds to approx. 24 days which means that the count will restart at
zero after this time period.
3.12.5 15-3* Alarm Log
Parameters in this group are array parameters, where up to 10 fault logs can be viewed. [0] is the most recent logged data, and [9] the oldest. Error
codes, values, and time stamp can be viewed for all logged data.
15-30 Alarm Log: Error Code
Array [10]
Range:
Function:
0 N/A*
[0 - 255 N/A]
View the error code and look up its meaning in the
Troubleshooting
chapter.
15-31 Alarm Log: Value
Array [10]
Range:
Function:
0 N/A*
[-32767 - 32767 N/A]
View an extra description of the error. This parameter is mostly used in combination with alarm 38
‘internal fault’.
15-32 Alarm Log: Time
Array [10]
Range:
Function:
0 s*
[0 - 2147483647 s]
View the time when the logged event occurred. Time is measured in seconds from frequency con-
verter start-up.
15-33 Alarm Log: Date and Time
Range:
Function:
0 N/A*
[0 - 0 N/A]
Array parameter; Date & Time 0 - 9: This parameter shows at which time the logged event occurred.
15-34 Alarm Log: Status
Range:
Function:
0 N/A*
[0 - 1 N/A]
Array parameter, status value 0 - 9. This parameter shows the status of the alarm:
0: Alarm inactive
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
130
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...