3.13 Main Menu - Data Readouts - Group 16
3.13.1 16-** Data Readouts
Parameter group for data read-outs, e.g. actual references, voltages, control, alarm, warning and status words.
3.13.2 16-0* General Status
Parameters for reading the general status, e.g. the calculated reference, the active control word, status.
16-00 Control Word
Range:
Function:
0 N/A*
[0 - 65535 N/A]
View the Control word sent from the frequency converter via the serial communication port in hex
code.
16-01 Reference [Unit]
Range:
Function:
0.000 Ref-
erenceFeed-
backUnit*
[-999999.000 - 999999.000 Refer-
enceFeedbackUnit]
View the present reference value applied on impulse or analog basis in the unit resulting from the
configuration selected in par.1-00
16-02 Reference [%]
Range:
Function:
0.0 %*
[-200.0 - 200.0 %]
View the total reference. The total reference is the sum of digital, analog, preset, bus, and freeze
references, plus catch-up and slow-down.
16-03 Status Word
Range:
Function:
0 N/A*
[0 - 65535 N/A]
View the Status word sent from the frequency converter via the serial communication port in hex
code.
16-05 Main Actual Value [%]
Range:
Function:
0.00 %*
[-100.00 - 100.00 %]
View the two-byte word sent with the Status word to the bus Master reporting the Main Actual Value.
16-09 Custom Readout
Range:
Function:
0.00 Cus-
tomReadou-
tUnit*
[-999999.99 - 999999.99 Custom-
ReadoutUnit]
View the user-defined readouts as defined in par.0-30
and par.0-32
.
3.13.3 16-1* Motor Status
Parameters for reading the motor status values.
16-10 Power [kW]
Range:
Function:
0.00 kW*
[0.00 - 1000.00 kW]
View the motor power in kW. The value shown is calculated on the basis of the actual motor voltage
and motor current. The value is filtered, and therefore approx. 30 ms may pass from when an input
value changes to when the data read-out values change.
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
134
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...