16-60 Digital Input
Range:
Function:
0 N/A*
[0 - 1023 N/A]
View the signal states from the active digital inputs. Example: Input 18 corresponds to bit no. 5, ‘0’
= no signal, ‘1’ = connected signal. Bit 6 works in the opposite way, on = '0', off = '1' (safe stop
input).
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/4
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. X30/2
Bit 10-63
Reserved for future terminals
130BA894.10
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
DI T-33
DI T-32
DI T-29
DI T-27
DI T-19
DI T-18
DI T-37
DI X30/4
DI X30/3
DI X30/2
DI X46/13
DI X46/11
DI X46/9
DI X46/7
DI X46/5
DI X46/3
DI X46/1
16-61 Terminal 53 Switch Setting
Option:
Function:
View the setting of input terminal 53. Current = 0; Voltage = 1.
[0] *
Current
[1]
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
16-62 Analog Input 53
Range:
Function:
0.000 N/A* [-20.000 - 20.000 N/A]
View the actual value at input 53.
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
138
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...