SiEBE18-526
Indoor Unit (SkyAir Models)
Function
99
2-2-a)-2 When a water level abnormality occurs during drain pump OFF
Occurrence of drain water level abnormality
80 sec
5min
5min
OFF
Drain pan
Water level abnormality
Normal
Error processing
Abnormal
Normal
Intermittent operation (*1)
Drain pump
ON
OFF
Compressor
ON
The abnormality is determined when 80 seconds elapse from compressor stop. Other than above,
behavior is same as 2-2-a).
Note : ((2-2-a)-2 When a water level abnormality occurs during drain pump OFF)
Recovery operation for drain water level abnormality does not activate when the water level can be
returned normal within A + 80 seconds.
5
sec
A
sec
2-2-b) Behavior when the unit restarts by remote control after the water level abnormality is recovered
Occurrence of drain water level abnormality
Recovery of drain water level abnormality
5min
5min
Intermittent operation (*1)
Drain pan
Water level abnormality
Normal
Remote control
ON
OFF
Drain pump
ON
OFF
Compressor
ON
OFF
Error processing
Abnormal
Normal
2 min
20 min
20min
Basic operation
Abnormal water level shall be cancelled simultaneausly when the unit is turned off with remote control
after recovery of abnormal water level. When the unit is turned on with remote control thereafter,
compressor starts operation 2 minutes later from the remote control ON. (Below diagram shows an
example of the case that the water level abnormality is recovered during the former 5 min intermittent
operation after the abnormality occurred during drain pump ON.)
Alarm indication will be turned off with the remote control OFF
operation after recovery of drain water level abnormality.
Compressor starts operation after 2 minutes from
remote control ON.
(When 3-min standby of compressor is complete.)
10
sec
A
sec
5
sec
3
min
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...