Function
Using Conditions
for Remote
Controller
Thermostat
(Applicable models: FHQ & FFQ only)
Remote controller thermostat is equipped only in wired remote controller.
Even when “ use remote controller thermostat ” is selected in service mode, the remote
controller thermostat may not be used.
< Conditions not to use >
1. When the remote controller thermostat malfunctions.
2. When the one remote controller group control is applied.
( Excluding simultaneous ON/OFF operation )
3. When conditions relating set temperature with remote controller and suction air temperature
are out of the operating zone of remote controller thermostat shown in below diagram.
( Excluding when automatic operation mode is selected. Whenever operation is in the
automatic mode, remote controller thermostat can be used. )
ts: Set temp. (°C)
For cooling
ts =
th + 3
ts = th + 1
ts = th - 1
ts = th - 3
Th: Suction air temp. (°C)
Differential zone
Remote control thermostat
operating zone
(S1118)
35
23
21
20
21 23
35
20
ts: Set temp. (°C)
For heating
ts = th + 1
ts = th - 1
ts = th - 10
ts = th - 12
Th: Suction air temp. (°C)
Differential zone
Remote control thermostat
operating zone
(S2746)
30
28
18
16
15
15
27
30
29
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...