Other Control
SiEBE18-526
74
Function
5. Other Control
5.1
Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using “Demand 1 Setting” or “Demand 2 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting” or
external input by external control adaptor is required.
[Demand 1 setting]
[Demand 2 setting]
H
Other protection control functions have precedence over the above operation.
5.2
Heating Operation Prohibition
Heating operation is prohibited above 30°CDB outdoor air temperature.
Setting
Standard for upper limit of power consumption
Demand 1 setting 1
Approx. 60%
Demand 1 setting 2 (factory setting)
Approx. 70%
Demand 1 setting 3
Approx. 80%
Setting
Standard for upper limit of power consumption
Demand 2 setting 1
Approx. 30%
Demand 2 setting 2 (factory setting)
Approx. 40%
Demand 2 setting 3
Approx. 50%