Pressure Sensor
SiEBE18-526
328
Troubleshooting
10.Pressure Sensor
High Pressure (P
H
)
Low Pressure (P
L
)
P
H
: Detected Pressure [High Side] MPa
P
L
: Detected Pressure [Low Side] MPa
V
H
: Output Voltage [High Side] V
DC
V
L
: Output Voltage [Low Side] V
DC
P
H
= 1.38V-0.69
P
L
= 0.57V-0.28
P
H
: High pressure (MPa)
V
L
: Low pressure (MPa)
V : Voltage (V)
Output Voltage (V
H,
V
L)
Detected Pressure
(V3053)
P
H
, P
L
MPa
5.0
51.0
45.9
40.8
35.7
4.5
4.0
3.5
30.6 3.0
25.5 2.5
20.4 2.0
15.3 1.5
10.2 1.0
5.1 0.5
0
-5.1 -0.5
-0.5
1.5
1
0.5
0
2.5
2
3.5
3
4
V
DC
(kg/cm³)