SiEBE18-526
Field Setting for SkyAir Indoor Unit
Test Operation
129
4.2
Field Setting
4.2.1 Wired Remote Controller
Note:
(Field setting must be made from the remote controller in accordance with the installation
conditions.)
Setting can be made by changing the “Mode number”, “FIRST CODE NO.”, and “SECOND
CODE NO.”.
Refer to the following procedures for Field setting.
Procedure
���
When in the normal mode, press the “
” button for a minimum of four seconds, and the FIELD
SET MODE is entered.
���
During group control, when setting by each indoor unit (mode No. 20, 21 and 23 have been
selected), push the “
” button and select the INDOOR UNIT NO to be set. (This operation is
unnecessary when setting by group.)
���
Select the desired MODE NO. with the “
” button.
���
Push the “
” button for about one second to return to the NORMAL MODE.
(Example) If
during group setting and the time to clean air filter is set to FILTER CONTAMINATION -
HEAVY, SET MODE NO. to “10,” FIRST CODE NO. to “0,” and SECOND CODE NO. to “02.”
���
Push the “
” button once and the present settings are SET.
���
Push the “
” lower button and select the SECOND CODE NO.
���
Push the “
” upper button and select FIRST CODE NO.
UNIT NO.
MODE NO.
SECOND
CODE NO.
FIRST
CODE NO.
FIELD
SET
MODE
2P068938-1
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...