Troubleshooting for SkyAir Indoor Unit
SiEBE18-526
286
Troubleshooting
Check No. 02
Check for Thermistors
Disconnect the thermistor connector from PCB, then measure the resistance by using a tester.
Thermistor temperature and resistance characteristics
Unit : k
Ω
Temperature
°C
A
B
-6.0
90.8
88.0
-4.0
81.7
79.1
-2.0
73.5
71.1
0.0
66.3
64.1
2.0
59.8
57.8
4.0
54.1
52.3
6.0
48.9
47.3
8.0
44.3
42.9
10.0
40.2
38.9
12.0
36.5
35.3
14.0
33.2
32.1
16.0
30.2
29.2
18.0
27.5
26.6
20.0
25.1
24.3
22.0
23.0
22.2
24.0
21.0
20.3
26.0
19.2
18.5
28.0
17.6
17.0
30.0
16.2
15.6
32.0
14.8
4.2
34.0
13.6
13.1
36.0
12.5
12.0
38.0
11.5
11.1
40.0
10.6
10.3
42.0
9.8
9.5
44.0
9.1
8.8
46.0
8.4
8.2
48.0
7.8
7.6
50.0
7.2
7.0
52.0
6.9
6.7
54.0
6.2
6.0
56.0
5.7
5.5
58.0
5.3
5.2
Application
z
Heat exchanger
(Indoor/Outdoor units)
z
Suction air
z
Remote controller
z
Air
z
Outdoor air
z
Suction pipe
z
Radiator fin
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...