SiEBE18-526
Troubleshooting for SkyAir Indoor Unit
Troubleshooting
277
5.7
Malfunction of Capacity Setting
Remote
Controller
Display
AJ
Applicable
Models
FFQ-B, FHQ-BU
Method of
Malfunction
Detection
Capacity is determined according to resistance of the capacity setting adaptor and the memory
inside the IC memory on the indoor unit PCB, and whether the value is normal or abnormal is
determined.
Malfunction
Decision
Conditions
Operation and:
(1)When the capacity code is not contained in the PCB’s memory, and the capacity setting
adaptor is not connected.
(2)When a capacity that doesn’t exist for that unit is set.
Supposed
Causes
Failure of capacity setting adaptor connection
Failure of indoor unit PCB
Troubleshooting
Note:
Capacity is factory set in the data IC on the PCB. A capacity setting adaptor that matches the
capacity of the unit is required in the following case.
If the indoor PCB installed at the factory is for some reason changed at the installation site, the
capacity will not be contained in the replacement PCB.
If you connect a capacity setting adaptor to a PCB in which the capacity is memorized, the
capacity setting for the PCB will become the capacity setting of the adaptor. (Priority of capacity
setting adaptor)
Turn the power supply off once
and back on.
Is AJ displayed on
the remote controller?
YES
YES
Plug a capacitor setting
adaptor that matches the
capacity of the unit into
X23A. (See note)
Bad contact of capacity
setting adaptor or
disconnected adaptor.
Indoor unit PCB
replacement
Could be outside cause
(noise, etc.) other than
malfunction.
Is the
capacity setting
adaptor plugged into X23A
of the indoor unit
PCB?
NO
(Q0415)
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...