SiEBE18-526
Indoor Unit (SkyAir Models)
Function
97
1-2 Operations when an occurrence of water level abnormality
1-2-a) Behavior between occurrence and recovery of water level abnormality
Occurrence of drain water level abnormality
1-2-b) Behavior when the unit restarts by remote control after the water level abnormality is recovered
Intermittent operation (*1)
5min
5min
Compressor
ON
OFF
Drain pan
Water level abnormality
Normal
Drain pump
ON
OFF
Error processing
Abnormal
Normal
After compressor stops due to water level abnormality, drain pump is operated intermittently, i.e. 5 min
ON, 5 sec OFF and 5 min ON. (*1) The intermittent operation is executed regardless of recovery of water
level abnormality during the intermittent operation. (*2) When the water level abnormality can not be
recovered, the latter 5 min ON operation is continued until recovery of the abnormality. (*3)
5
sec
10
sec
A
sec
*2
Even though the water level
abnormality could be recovered
during intermittent operation, the
operation shall be carried out
without exception.
*3
If the abnormality could not be recovered
during intermittent operation, the latter 5
min ON operation is continued until
recovery of the abnormality.
Water level abnormality shall be cancelled simultaneausly when the unit is turned off with remote control
after recovery of the water level abnormality. When the unit is turned on with remote control thereafter,
compressor starts operation 2 minutes later from the remote control ON. (Below diagram shows an
example of the case that the water level abnormality is recovered during the former 5 min intermittent
operation.)
Occurrence of drain water level abnormality
Recovery of drain water level abnormality
ON
2 min
Compressor
ON
OFF
Error processing
Abnormal
Normal
Remote control
5min
Drain pan
Water level abnormality
Normal
Drain pump
ON
OFF
OFF
5
sec
10
sec
A
sec
Note : (1 On the whole of cooling and dry operation)
Recovery operation for drain water level abnormality does not activate when the water level can
be returned normal within A + 10 seconds.
Alarm indication will be turned off with the remote control
OFF operation after recovery of drain water level abnormality.
Compressor starts operation after 2 minutes from
remote control ON.
(When 3-min standby of compressor is complete.)
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...