Special Control
SiEBE18-526
64
Function
3.3
Defrosting Operation
The defrost operation is performed to solve frost on the outdoor unit heat exchanger when
heating, and the heating capacity is recovered.
[Conditions to start]
The defrost operation is started referring following conditions.
Outdoor heat exchanger heat transfer co-efficiency
Temperature of heat-exchange (Tb)
Low pressure equivalent saturation temperature (Te)
Timer (2 hours at the minimum)
In addition, outdoor heat-exchange co-efficiency is derived from Tc, Te, and the compressor
load.
* From the preparing operation to the defrost operation, and from the defrost operation to the
operation after defrost, the compressor stops for 110 sec. to reduce noise on changing of the
four way valve.
Outdoor unit actuator
Defrost preparation
operation
Defrost operation
Post Defrost operation
Compressor
Upper limit control
140 Hz
2-step increase from
52 Hz to
(Pc - Pe>0.4 MPa)
every 20 sec.
Outdoor unit fan
STEP8
OFF
STEP8
Four way valve
ON
OFF
ON
Main electronic expansion valve
(EV1)
SH control
2000 pls
200~400 pls
Subcooling electronic expansion
valve (EV2)
0 pls
0 pls
0 pls
Hot gas bypass valve (SVP)
OFF
ON
ON
Receiver gas discharging valve
(SVG)
ON
→
OFF
ON
→
OFF
ON
→
OFF
Ending conditions
130 sec.
•
Max. 18 min.
•
Tb >11
°
C
•
160 sec.
•
Pc - Pe>0.4MPa
or
or
Indoor actuator
During defrost
Indoor unit fan
Thermostat ON unit
OFF
Stopping unit
OFF
Thermostat OFF unit
OFF
BP unit electronic expansion
valve
Thermostat ON unit
SH control
Stopping unit
80 pls
Thermostat OFF unit
SH control
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...