System Configuration
193
2.2.13 Note for Multi System
Note for Multi System
<<
What is a “Multi System”? >>
This system has one outdoor unit connected to multiple indoor units.
Functions depend on the model.
Outdoor
unit
Selecting the Operation Mode
1. With the Priority Room Setting
present but inactive or not present
When more than one indoor unit is operating, priority is
given to the first unit that was turned on.
In this case, set the units that are turned on later to the
same operation mode (*1) as the first unit.
Otherwise, they will enter the Standby Mode, and the operation lamp will flash; this does not indicate malfunction.
(*1)
• COOL,
DRY
and FAN mode may be used at the same time.
• AUTO
mode
automatically selects COOL mode or HEAT mode based on the room temperature.
Therefore, AUTO mode is available when selecting the same operation mode as that of the room
with the first unit to be turned on.
<CAUTION>
Normally, the operation mode in the room where the unit is first run is given priority, but the following situations are
exceptions, so please keep this in mind.
If the operation mode of the first room is
FAN Mode
, then using
Heating Mode
in any room after this will give priority to
heating.
In this situation, the air conditioner running in FAN Mode will go on standby, and the operation lamp will flash.
Living
room
C
room
B
room
A
room
OUTDOOR UNIT SILENT Operation
NIGHT QUIET Mode (Available only for cooling operation)
NIGHT QUIET Mode requires initial programming during installation. Please consult your retailer or dealer for assistance.
NIGHT QUIET Mode reduces the operation noise of the outdoor unit during the night time hours to prevent
annoyance to neighbors.
• The NIGHT QUIET Mode is activated when the temperature drops 5
°
C or more below the highest temperature
recorded that day. Therefore, when the temperature difference is less than 5
°
C, this function will not be activated.
• NIGHT QUIET Mode reduces slightly the cooling efficiency of the unit.
The Cooling / Heating Mode Lock requires initial programming during installation.Please consult your retailer or dealer
for assistance. The Cooling / Heating Mode Lock sets the unit forcibly to either Cooling or Heating Mode. This function
is convenient when you wish to set all indoor units connected to the Multi system to the same operation mode.
Cooling / Heating Mode Lock (Available only for heat pump models)
When using the OUTDOOR UNIT SILENT operation feature with the Multi system, set all indoor units to
OUTDOOR UNIT SILENT operation using their remote controls.
When clearing OUTDOOR UNIT SILENT operation, clear one of the operating indoor units using their remote control.
However OUTDOOR UNIT SILENT operation display remains on the remote control for other rooms.
We recommend you release all rooms using their remote controls.
1. With the Priority Room Setting present but inactive or not present
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...