SiEBE18-526
Indoor Unit (SkyAir Models)
Function
103
Mode Conflict
[Overview]
While the indoor unit for another room and the outdoor unit are operating, when the indoor unit
for the own room is activated, the operation mode which can be selected in the own room has
some restrictions as mentioned below.
i)
In case an priority for operation mode selection is given to the own room by setting the dip
switch of outdoor unit;
→
The own room can be operated in any mode.
ii)
In case an priority for operation mode selection is not given to the own room by setting the
dip switch of outdoor unit;
→
The unit can be operated as follows:
{
:Operational
∗:
The unit for another room is switched into non-operational condition.
× : Non-operational
* Operation of the indoor unit for the own room during non-operation.
•
Fan = OFF
•
Louver = becomes horizontal position.
•
ON LED on the remote controller = blinks.
•
Indication of "under central control" on the remote controller = displayed.
Note:
During automatic operation, at the time of changing operation mode to Automatic cooling
or Automatic heating, the unit is operated as the table shown above.
Outdoor unit
operation mode
when an operation
mode for the own
room is selected.
(The outdoor unit
is operated in the
mode as
mentioned below.)
Operation mode selected in the own room
Cooling or
Automatic cooling
(Note)
Dry
Blowing
Heating or
Automatic heating
(Note)
Cooling
{
{
{
×
Heating
×
×
×
{
Blowing
{
{
{
{
∗
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...