Troubleshooting for RA Indoor Unit
SiEBE18-526
264
Troubleshooting
4.5
Shutter Drive Motor / Shutter Limit Switch Abnormality
Remote
Controller
Display
C7
Method of
Malfunction
Detection
The shutter open / close performance is detected by the limit switch attached on its structure. In
this way, the shutter drive motor and the shutter limit switch are checked for failure.
Malfunction
Decision
Conditions
When the shutter is open, the limit switch is closed.
Supposed
Causes
Shutter drive motor defective
Shutter limit switch defective
Shutter itself deformed (warped)
Shutter's sealing material too thick
Detection error by broken relay harness or disconnected connector
Detection error due to defective PCB (2)
Foreign substance in blow port
Troubleshooting
Check No.03
Refer to P.265
Turn off the power.
Check No. 03
Check the limit switch continuity.
Remove such substance.
Replace the limit switch.
Reconnect the connector or
replace the relay harness.
Replace the shutter drive
motor or the PCB (2).
Check the shutter's sealing
material.
Check the shutter for
deformation or its sealing
material.
(Q0410)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Foreign substance in
the shutter structure?
YES
NO
NO
NO
YES
Shutter closed?
NO
Shutter opening itself?
YES
YES
YES
NO
Relay harness
broken or connector
disconnected?
Limit switch on power?
Open the shutter and turn on the
power.
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...