Troubleshooting for Outdoor Unit
SiEBE18-526
314
Troubleshooting
7.20 Malfunction of Inverter Radiating Fin Temperature Rise
Sensor
Remote
Controller
Display
P4
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Resistance of radiation fin thermistor is detected when the compressor is not operating.
Malfunction
Decision
Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status.
Malfunction is not decided while the unit operation is continued.
"P4" will be displayed by pressing the inspection button.
Supposed
Causes
Defect of radiator fin temperature sensor
Defect of inverter PCB
Troubleshooting
∗
Refer to thermistor resistance / temperature characteristics table on P326.
(Q0440)
After resetting, restart.
YES
YES
Is the
resistance of thermistor
correct?
Is the resetting possible?
Replace inverter PCB.
Measure the resistance of
radiation fin thermistor.
NO
Replace inverter PCB.
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...