SiEBE18-526
Indoor Unit (RA Models)
Function
89
7.9
HOME LEAVE Operation
Outline
In order to respond to the customer's need for immediate heating and cooling of the room after
returning home or for house care, a measure to switch the temperature and air volume from that
for normal time over to outing time by one touch is provided. (This function responds also to the
need for keeping up with weak cooling or heating.)
This time, we seek for simplicity of operation by providing the special temperature and air
volume control for outing to be set by the exclusive button.
Detail of the
Control
1. Start of Function
The function starts when the [HOME LEAVE] button is pressed in cooling mode or heating
mode (including stopping and powerful operation). If this button is pressed while the operation is
stopped, the function becomes effective when the operation is started. If this button is pressed
in powerful operation, the powerful operation is reset and this function becomes effective.
The [HOME LEAVE] button is ineffective in dry mode and fan mode.
2. Details of Function
A mark representing [HOME LEAVE] is indicated on the liquid crystal display of the remote
controller. The indoor unit is operated according to the set temperature and air volume for
HOME LEAVE which were pre-set in the memory of the remote controller.
The LED (Red) of indoor unit representing [HOME LEAVE] lights up. (It goes out when the
operation is stopped.)
3. End of Function
The function ends when the [HOME LEAVE] button is pressed again during [HOME LEAVE]
operation or when the powerful operation button is pressed.
Others
The set temperature and set air volume are memorized in the remote controller. When the
remote controller is reset due to replacement of battery, it is necessary to set the temperature
and air volume again for [HOME LEAVE].
Scene <Cooling>
“Home leave
operation”
set temp.
Start “Home leave operation”
Stop “Home leave operation”
Time
(R1366)
Home leave operation
Set temp.
Normal operation
Normal operation
Scene <Heating>
“Home leave
operation”
set temp.
Start “Home leave operation”
Stop “Home leave operation”
Time
(R1367)
Home leave operation
Set temp.
Normal operation
Normal operation
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...