SiEBE18-526
Indoor Unit (RA Models)
Function
85
7.6
Night Set Mode
When the OFF timer is set, the Night Set circuit automatically activates.
The Night Set circuit maintains the airflow setting made by users.
The Night Set
Circuit
The Night Set circuit continues heating or cooling the room at the set temperature for the first
one hour, then automatically raises the temperature setting slightly in the case of cooling, or
lowers it slightly in the case of heating, for economical operations. This prevents excessive
heating in winter and excessive cooling in summer to ensure comfortable sleeping conditions,
and also conserves electricity.
Cooling
Operation
In case of FTXS20-35D and CTXS50D, the temperature rises once.
Heating
Operation
Timer operation
Night Set Circuit ON
+0.5°C
temperature shift
Operation stops
at the set hours
1 hour
Temperature
s1°C
Temperature
s0.5°C
Temperature
setting
0.5°C
0.5°C
30 minutes
(R1361)
+0.5°C temperature shift
Temperature setting remains the same
: • When outside temperature is normal and room
temperature is at set temperature.
: • When outside temperature is high (27°C or higher).
Timer operation
Night Set Circuit ON
+0.5°C
temperature shift
Operation stops
at the set hours
Temperature
s0.5°C
Temperature
setting
0.5°C
(R4421)
2°C
1 hour later
Timer operation
Night Set Circuit ON
Thermostat
setting
(R1362)
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...