BP Unit Control
SiEBE18-526
78
Function
6.3
SH Control in Cooling Operation
Purpose of the
Function
This function ensures appropriate refrigerant distribution when many room units are operating in
the cooling mode.
Outline
The heat exchanger temperatures and gas pipe temperatures of operating room units are
detected by the gas pipe thermistors, and the electronic expansion valves' flow rates are
corrected so as to adjust the difference between heat exchanger temperature and gas pipe
temperature of each room unit (hereafter referred to as SH) close to the target values.
When SH is higher than target value
→
Opens the valve of that room unit
When SH is lower than target value
→
Closes the valve of that room unit
When the liquid pipe temperature is lower than the heat exchanger temperature, the electronic
expansion valve is opened more than normal opening.
(Protection function to prevent rotor dew condensation)
The gas pipe temperature and indoor heat exchanger temperature are detected at the time of
every sampling time of 40 sec for the cooling SH control.
In order to prevent dew condensation in connection pipe, gas pipe lower-limit temperature is set
as follows.
Outdoor Temperature
Gas Pipe Lower-Limit Temperature
-5
-22
0
-17
5
-12
10
-6
15
-1
20
4
25
8
30
8
35
8
40
8
45
8
0
2
4
6
8
10
12
-20
0
20
40
60
Outdoor air temperature
Gas pipe lo
w
er-limit temper
ature
(Q0378)
Gas pipe lower-limit temperature = × DOA - 17 (however 8ºC or lower)
DOA:Outdoor air temperature
240
256
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...