SiEBE18-526
List of Malfunction Code
Troubleshooting
255
3. List of Malfunction Code
9
: Blink
8
: ON
7
: OFF
Malfunction
code
Malfunction contents
Page Referred
RA Indoor
Unit
SkyAir
Indoor Unit
BP Unit
Outdoor
Unit
Indoor
Unit
A0
Error of external protection device
—
—
—
—
A1
PC board defect, E
2
PROM defect
257
268
—
—
A3
Malfunction of drain level control system (33H)
—
269
—
—
A5
Freeze-up protection or high pressure control
258
—
—
—
A6
Fan motor (MF) lock, overload
260, 261
272, 273
—
—
A7
Malfunction of swing flap motor (MA)
—
275
—
—
A9
Malfunction of electronic expansion valve (20E)
—
—
287
—
AF
Drain pump error
—
271
—
—
AJ
Malfunction of capacity setting
—
277
—
—
C4
Malfunction of thermistor (R2T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
263
278
—
—
C5
Malfunction of thermistor (R3T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
—
279
—
—
C7
Shutter drive motor / shutter limit switch abnormality
264
—
—
—
C9
Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
263
280
—
—
CA
Malfunction of thermistor for air outlet (loose
connection, disconnection, short circuit, failure)
—
—
—
—
CJ
Malfunction of thermostat sensor in remote controller
—
281
—
—
Outdoor
Unit
E1
PC board defect, E
2
PROM defect
—
—
—
294
E2
Faulty BP unit PCB
—
—
288
—
E3
Actuation of high pressure switch
—
—
—
295
E4
Actuation of low pressure switch
—
—
—
296
E5
Compressor motor lock
—
—
—
297
E6
Standard compressor lock or over current
—
—
—
—
E7
Malfunction of outdoor unit fan motor
—
—
—
298
E9
Malfunction of moving part of electronic expansion
valve (Y1E~2E)
—
—
—
299
F3
Abnormal discharge pipe temperature
—
—
—
300
F6
Refrigerant overcharged
—
—
—
—
H3
Malfunction of high pressure switch
—
—
—
—
H4
Actuation of low pressure switch
—
—
—
—
H7
Abnormal outdoor fan motor signal
—
—
—
—
H9
Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
—
—
—
301
J0
Faulty BP liquid or gas pipe thermistor
—
—
289
—
J2
Current sensor malfunction
—
—
—
—
J3
Malfunction of discharge pipe thermistor (R3T) (loose
connection, disconnection, short circuit, failure)
—
—
—
302
J5
Malfunction of thermistor (R2T) for suction pipe
(loose connection, disconnection, short circuit,
failure)
—
—
—
303
J6
Malfunction of thermistor (R4T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
—
—
—
304
J7
Malfunction of header thermistor
—
—
—
—
J8
Malfunction of thermistor (R7T) for oil equalizing pipe.
(loose connection, disconnection, short circuit,
failure)
—
—
—
—
J9
Malfunction of receiver gas pipe thermistor (R5T)
—
—
—
305
JA
Malfunction of discharge pipe pressure sensor
—
—
—
306
JC
Malfunction of suction pipe pressure sensor
—
—
—
307
L0
Inverter system error
—
—
—
—
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...