SiEBE18-526
Special Control
Function
65
3.4
Pump-down Residual Operation
When activating compressor, if the liquid refrigerant remains in the heat-exchanger, the liquid
enters into the compressor and dilutes oil therein resulting in decrease of lubricity.
Therefore, the pump-down residual operation is performed to collect the refrigerant in the heat-
exchanger when the compressor is down.
3.4.1 Pump-down Residual Operation in Cooling Operation
3.4.2 Pump-down Residual Operation in Heating Operation
3.5
Restart Standby
Restart is stood by force to prevent frequent power-on/off and to equalize pressure in the
refrigerant system.
Actuator
Outdoor unit operation
Compressor
124 Hz
Outdoor unit fan
Fan control
Four way valve
OFF
Main electronic expansion valve (EV1)
2000 pls
Subcooling electronic expansion valve
(EV2)
0 pls
Hot gas bypass valve (SVP)
OFF
Receiver gas discharging valve (SVG)
ON
→
OFF
Ending conditions
•
30 sec.
•
Pe<0.5 MPa
•
Td>110
°
C
or
Actuator
Outdoor unit operation
Compressor
52
→
124 Hz
Outdoor unit fan
STEP8
Four way valve
ON
Main electronic expansion valve (EV1)
0 pls
Subcooling electronic expansion valve
(EV2)
0 pls
Hot gas bypass valve (SVP)
ON
→
OFF
Receiver gas discharging valve (SVG)
ON
→
OFF
Ending conditions
•
3 min.
•
Pe<0.25 MPa
•
Td>110
°
C
or
Actuator
Operation
Remarks
Compressor
OFF
⎯
Outdoor unit fan
OFF
⎯
Four way valve
Keep former condition.
⎯
Main electronic expansion valve (EV1)
0 pls
⎯
Subcooling electronic expansion valve
(EV2)
0 pls
⎯
Hot gas bypass valve (SVP)
OFF
→
ON
⎯
Receiver gas discharging valve (SVG)
OFF
⎯
Ending conditions
5 min.
⎯
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...