SiEBE18-526
Special Control
Function
61
3. Special Control
3.1
Startup Control
On activation, following control is performed to lighten load of the compressor by back liquid and
the like. Also, the position of the four way valve is defined.
3.1.1 Startup Control in Cooling Operation
3.1.2 Startup Control in Heating Operation
Actuator
Operation
Remarks
Compressor
Differential pressure control
Compressor operating frequency
increases by 2 step / 20 sec until
Pc - Pe>0.4 MPa.
Outdoor unit fan
High pressure control
Initial fan speed is set to STEP 0
(Ta
<
20°C), or STEP 7 (Ta
≥
).
Four way valve
OFF
⎯
Main electronic expansion valve (EV1)
2000 pls
⎯
Subcooling electronic expansion valve
(EV2)
0 pls
⎯
Hot gas bypass valve (SVP)
ON
⎯
Receiver gas discharging valve (SVG)
OFF
⎯
Ending conditions
•
255 sec.
•
Pc - Pe>0.4 MPa
•
75 sec
BP unit electronic expansion valve
(operating room)
0 pls
⎯
BP unit electronic expansion valve
(stopping room)
0 pls
⎯
Actuator
Operation
Remarks
Compressor
Differential pressure control
Compressor operating frequency
increases by 2 step / 20 sec until
Pc - Pe>0.4 MPa.
Outdoor unit fan
STEP8
⎯
Four way valve
ON
⎯
Main electronic expansion valve (EV1)
180 pls
⎯
Subcooling electronic expansion valve
(EV2)
0 pls
⎯
Hot gas bypass valve (SVP)
ON
⎯
Receiver gas discharging valve (SVG)
ON
⎯
Ending conditions
•
225 sec.
•
Pc - Pe>0.4 MPa
•
40 sec
BP unit electronic expansion valve
(operating room)
0 pls
⎯
BP unit electronic expansion valve
(stopping room)
0 pls
⎯
or
&
(
or
&
(
Содержание Super Multi Plus D-Series
Страница 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Страница 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Страница 167: ...Instruction SiEBE18 526 156 System Configuration FDXS25 35C CDXS50 60C 3 6 8 9 10 7 1 4 5 2 Names of parts Indoor Unit...
Страница 249: ...Instruction SiEBE18 526 238 System Configuration...
Страница 395: ...2 5 DS1 3 DS1 4 BP Unit ON OFF Connect BP unit Not connect BP unit Do not change the factory setting Not Used...