Document no.:
S-4-007.875/E
Prepared: 2002-10-01
BM
Revision:
R5 2004-04-07 BM
©
2002, Consilium Marine AB
Service manual
Appendix C: Fault codes C-13
CS3000
181.
SHORT CIRCUIT ON SUBLOOP
Cause
Remedy
Short circuit on subloop.
Check cable.
182
CABLE BREAK
Cause
Remedy
A cable break has been detected.
Check corresponding cables.
183
CABLE OVERLOAD, CURRENT LIMIT REACHED
Cause
Remedy
There is an overload in the cable.
Check if too many units are
connected to the cable. Compare
with cable data.
184
POWER FAULT
Cause
Remedy
The power supply is lost.
Check power generation.
185
LOSS OF CAPACITY TO CHARGE BATTERY
Cause
Remedy
The battery charger is unable to charge the
battery.
Check the battery charger and the
battery.
186
EXTERNAL FAULT
Cause
Remedy
Fault from input.
Check cable and/or external unit.
187
DOUBLE ADDRESS ON LOOP
Cause
Remedy
Check the offending units against
drawings.
Set correct addresses for the units,
with the DIP-switches.