Service Manual CS3000
Chapter 1: Service mode 1-1
Control unit
Document no.:
S-4-007.875/E
Prepared:
1995-03-17 Fia
Revision:
R4 2004-03-15 BM
© 1995, Consilium Marine AB
Chapter 1: Control unit
Service mode
The control unit includes a fourth access level to be used only by the service
engineer. There are two functions in the service mode: bypass the built-in short
circuit isolators and definition of control unit address.
Set address
(Access level 4)
Each control unit in the system must have a unique address in the interval 217
- 232. The control unit number must correspond with the number defined in
the Definition program. The control unit address must be set after the system
definition is downloaded and the system is restarted.
•
Press F4 (MENU) until SERVICE is displayed on line 4.
•
Press F1 (SERVICE).
•
Press F1 (ADDRESS).
•
Enter the address for the control unit. The address interval is 217 - 232.
Bypass built-in short circuit isolators
The built-in short circuit isolators, two on each loop, are bypassed when you
activate the SERVICE function. The short circuit isolators remain bypassed
until you activate them again.
•
Press F4 (MENU) until SERVICE is displayed on line 4.
•
Press F1 (SERVICE).