Document no.:
S-4-007.875/E
Prepared: 2002-10-01
BM
Revision:
R5 2004-04-07 BM
©
2002, Consilium Marine AB
Service manual
Appendix C: Fault codes C-2
CS3000
4 ADDITIONAL
CENTRAL
The central unit found an additional sub-central unit after cold start.
Cause
Remedy
Wrong definition of number of central
units.
Check the specification and
redefine the system.
5 LOOP(S)
MISSING
The main central unit is missing a loop after cold start.
Cause
Remedy
SPK-2 or LPK-2 has a hardware fault.
Exchange the board.
Wrong definition of number of loops.
Check the specification and
redefine the system.
6 ADDITIONAL
LOOP(S)
The central unit found an additional loop after cold start.
Cause
Remedy
Wrong definition of number of loops.
Check the specification and
redefine the system.
7
MISSING LOOP UNIT
Fewer loop units have been found than defined in the loop.
Cause
Remedy
Wrong definition of number of loop units.
Check the specification and
redefine the system.
Loop unit connections faulty.
Connect the unit correctly
Missing answer from a loop unit.
Exchange the unit.
8
ADDITIONAL LOOP UNIT(S)
More loop units have been found than defined in the loop.
Cause
Remedy
Wrong definition of number of loop units.
Check the specification and
redefine the system.
Loop unit connections faulty.
Connect the unit correctly.
11
LOOP MISSING DEF. DATA
Cause
Remedy
The loop has not been defined properly at
the installation.
Redefine the loop.