Document no.:
S-4-007.875/E
Prepared: 2002-10-01
BM
Revision:
R5 2004-04-07 BM
©
2002, Consilium Marine AB
Service manual
Appendix C: Fault codes C-10
CS3000
142 EARTH
FAULT–
Cause
Remedy
Earth fault between negative terminal and
earth.
See
Earth fault
at the end of this
chapter.
FAULT (142) POWER EARTH FAULT –
Earth fault to minus from the power unit.
145 LOW
VOLTAGE
Cause
Remedy
Too low system voltage from the power
unit.
Test the rectifier and measure the
voltage. If necessary exchange the
rectifier.
146 HIGH VOLTAGE (Abnormal. condition)
Cause
Remedy
Too high system voltage from power unit.
Test the rectifier and measure the
voltage. If necessary exchange the
rectifier.
147 FIRE
PREWARNING
Cause
Remedy
The system has detected a smoke value
approaching the alarm level.
Check the unit.
150 TIMER
STUCK
Cause
Remedy
The timer does not work properly.
Check the unit.
161 DOOR
OPEN
Cause
Remedy
A door is still open one minute after the
instruction to close it was sent.
Check the door.
163 OPEN DOOR SUBLOOP BREAK
Cause
Remedy
Cable break between module and open
door sensor.
Mend the cable.