Document no.:
S-4-007.875/E
Prepared: 2002-10-01
BM
Revision:
R5 2004-04-07 BM
©
2002, Consilium Marine AB
Service manual
Appendix C: Fault codes C-1
CS3000
Appendix C: Fault codes CS3000 version 6
Listed below are all fault codes, their causes and how an operator with some
knowledge of the system can solve the problem. When a fault occurs, localise
the problem and deal with it.
The word FAULT is displayed on the first line of the display together with a
fault code, followed by the zone number and the address for the loop unit
causing the problem, if the system has this information. Additional text is
displayed on line two, if provided. A few fault codes cannot be displayed with
all this information. These fault codes are marked with an asterisk (
*
) in the
summary below.
FIRE IN SYSTEM
There is a fire alarm in the system and the LPK board is not answering.
1
MISSING CONTROL UNIT
The central unit is missing a control unit after cold start.
Cause
Remedy
System loop break.
Mend the cable.
Control unit incorrectly addresses.
Check and readdress the control
unit.
Hardware fault in the control unit.
Exchange the unit.
Wrong number of control units in the
definition.
Check the specification and
redefine the system.
2
ADDITIONAL CONTROL UNIT
The central unit found an additional control unit after cold start.
Cause
Remedy
Wrong definition of number of control
units.
Check the specification and
redefine the system.
3 MISSING
CENTRAL
The main central unit is missing a sub-central after cold start.
Cause Remedy
LPK-2 in a central unit is incorrectly
addressed.
Set a valid address.
System loop break.
Mend the cable.
LPK-2 has a hardware fault.
Exchange the board.
Wrong definition of number of repeater
panels.
Check the specification and
redefine the system.