Document no.:
S-4-007.875/E
Prepared: 2002-10-01
BM
Revision:
R5 2004-04-07 BM
©
2002, Consilium Marine AB
Service manual
Appendix C: Fault codes C-12
CS3000
174
NO POWER SUPPLY FOR LOOP
Cause
Remedy
No power feed from the pcb.
DC/DC converter faulty.
175
DOOR IN WRONG POSITION
Cause
Remedy
Door in wrong position.
Check for obstruction.
176
CABLE BREAK POSITIVE SIDE
Cause
Remedy
Check for a cable break on positive lead.
Mend the cable break.
A tripped short circuit isolator can cause
this fault.
Check the short circuit isolators.
177
CABLE BREAK NEGATIVE SIDE
Cause
Remedy
Check for a cable break on negative lead.
Mend the cable break.
A tripped short circuit isolator can cause
this fault.
Check the short circuit isolators.
178
WRONG TYPE OF LOOP UNIT FOUND
Cause
Remedy
Check the ID setting of the faulty unit.
Set a correct value on the DIP-
switch of the unit.
179
UNABLE TO DETECT SHORT CIRCUIT
Cause
Remedy
Unable to detect short circuit.
Exchange loop-PCB.
180
SPRINKLER VALVE CLOSED
Cause
Remedy
Sprinkler valve closed.
Check why it is closed.