Service manual CS3000
Chapter 3: Power unit KE-2 3-46
The circuit boards of the central unit
Document no.:
S-4-007.875/E
Prepared:
1995-03-17 Fia
Revision:
R2 2002-08-14 BM
© 1995, Consilium Marine AB
Technical data
Mains/emergency voltage:
230 V +10%/-15%
Mains/emergency frequence:
50-60 Hz
Output current :
I
min
: 0.1 A
I
max
: 20 A
*
Output voltage:
U
out
: 23 - 26 VDC
U
rip
:
±
0.2 VDC
*
Output current is of higher priority than battery charging current. If the
output current exceeds 8 A the battery charging current will decrease. The
battery charging current is equal to zero when the output current is equal to
20 A.
Battery charging
Charging current:
I
charge
: 0 - 10 A
**
Charging voltage:
U
charge
: 21.5 - 34.0
±
0.2 VDC
**
The charging current and the charging voltage can be set individually for
the different charging phases. The charging current can be set between 0-10
A and the charging voltage can be set between 21 - 34 VDC.