Service manual
Appendix C: Fault codes C-5
CS3000
30
CONTROL UNIT X NO POLL FROM MAIN CENTRAL
There is no contact between control unit x and the main central unit.
Cause
Remedy
The LPK in the main central unit is not
answering.
The LPK is faulty. Replace it.
Cable break in the system loop.
Check the cable.
41 BOOTED
A loop in the system has generated a boot signal.
Cause
Remedy
The system is booting. Which PCB that is
booting is shown in the display.
Reset the fault.
42 BOOT
DISABLED
A loop unit was disconnected by the system during the initialisation.
Cause
Remedy
Loop unit faulty.
Exchange the section unit.
Address unit on a sub-loop is faulty.
Test the sub-loop.
43
WRONG ADDRESS INTERVAL
The loop unit address interval set for a timer is wrong.
Cause
Remedy
Overlapping address intervals.
Set a valid address interval.
End-address of the interval is lower then
the start-address.
Set a valid address interval.
44 ILLEGAL
ADDRESS
The received address does not correspond with the sent address.
Cause
Remedy
Loop unit faulty.
Exchange the loop unit.
51
LOOP OUTPUT MISSING
Cause
Remedy
The loop unit has no active outputs. Error
in the site set-up.
Download new set-up data.