Service Manual CS3000
Appendix B: Fault codes
B-2
Fault codes
Document no.:
S-4-007.875/E
Prepared:
1995-03-17 Fia
Revision:
R4 2004-03-15 BM
©
2002, Consilium Marine AB
4
ADDITIONAL CENTRAL UNIT
An additional sub-central is found by the central unit after cold start.
Cause
Remedy
Wrong definition of number of
central units.
Check the specification and
redefine the system.
5 SECTION(S)
MISSING
The main central unit is missing a section after cold start.
Cause
Remedy
SPK-2 or LPK-2 has a hardware
fault.
Exchange the board.
Wrong definition of number of
sections.
Check the specification and
redefine the system.
6 ADDITIONAL
SECTION(S)
An additional section has been found by the central unit after cold start.
Cause
Remedy
Wrong definition of number of
sections.
Check the specification and
redefine the system.
7
MISSING SECTION UNIT(S)
Fewer section units has been found than defined in the loop.
Cause
Remedy
Wrong definition of number of
section units.
Check the specification and
redefine the system.
Section unit connections faulty.
Connect the unit correctly
Missing answer from a section
unit.
Exchange the unit.
8
ADDITIONAL SECTION UNIT(S)
More section units have been found than defined in the loop.
Cause
Remedy
Wrong definition of number of
section units.
Compare the installation with the
drawings. Redefine the system.
Section unit connections faulty.
Connect the unit correctly.