![Consilium Salwico CS3000 Скачать руководство пользователя страница 58](http://html1.mh-extra.com/html/consilium/salwico-cs3000/salwico-cs3000_service-manual_2655086058.webp)
Service Manual CS3000
Appendix B: Fault codes
B-1
Fault codes
Document no.:
S-4-007.875/E
Prepared:
1995-03-17 Fia
Revision:
R4 2004-03-15 BM
©
2002, Consilium Marine AB
Appendix B: Fault codes CS3000 version 4
All the fault codes, their cause and how an operator with some knowledge of the
system can solve the problem, are listed below. When a fault occurs, localise the
problem and deal with it.
The word FAULT is displayed on the first line of the display together with a fault
code followed by the section number and the address for the section unit causing the
problem, if the system has this information. Additional text is displayed on line two, if
provided. A few fault codes can not be displayed with all this information. These fault
codes are marked with an asterisk (
*
) in the summary below.
1
CONTROL UNIT MISSING
The central unit is missing a control unit after cold start.
Cause
Remedy
System loop break.
Mend the cable.
Control unit incorrectly
addressed.
Check and readdress the control
unit.
Hardware fault in the control
unit.
Exchange the unit.
Wrong number of control units
in the definition.
Check the specification and
redefine the system.
2
ADDITIONAL CONTROL UNIT
An additional control unit is found by the central unit after cold start.
Cause
Remedy
Wrong definition of number of
control units.
Check the specification and
redefine the system.
3
MISSING CENTRAL UNIT
The main central unit is missing a sub-central after cold start.
Cause
Remedy
LPK-2 in a central unit is
incorrectly addressed.
Set a valid address.
System loop break.
Mend the cable.
LPK-2 has a hardware fault.
Exchange the board.
Wrong definition of number of
repeater panels.
Check the specification and
redefine the system.