Document no.:
S-4-007.875/E
Prepared: 2002-10-01
BM
Revision:
R5 2004-04-07 BM
©
2002, Consilium Marine AB
Service manual
Appendix C: Fault codes C-11
CS3000
164 DOOR CLOSED SUBLOOP BREAK
Cause
Remedy
Cable break between module and closed
door sensor.
Mend the cable.
166
DAMPER /DOOR SHOULD HAVE BEEN OPENED
Cause
Remedy
Damper/door in wrong position.
Check for obstruction.
167
DAMPER /DOOR SHOULD HAVE BEEN CLOSED
Cause
Remedy
Damper/door in wrong position.
Check for obstruction.
170
SENSOR FAULT
The detector is giving a too low analogue value.
Cause
Remedy
The detector has a faulty sensor element.
Replace the detector.
NB
This fault could be the result of air
blowing at the unit.
Check the location of the detector
and if need be, move it to a less
windy location.
171
CABLE BREAK FROM INPUT 1
Cause
Remedy
There is a cable break on input 1.
Check the cable.
172
CABLE BREAK FROM INPUT 2
Cause
Remedy
There is a cable break on input 2.
Check the cable.
173
DOOR FEEDBACK
Cause
Remedy
There is no response from the door-
holding relay.
Check the door-holder relay and its
cable.