Service manual CS3000
Chapter 3: Relay board ARK-2 3-15
The circuit boards of the central unit
Document no.:
S-4-007.875/E
Prepared:
1995-03-17 Fia
Revision:
R4 2004-03-15 BM
© 2002, Consilium Marine AB
Jumper "PLUS"
With this jumper the pulse type can be altered. In the left position the pulse is
internally generated, in the right position the pulse comes from an external
source.
Switch S9
This switch is found on the front panel and is used for resetting the basic-
alarm.
Switch SW1
SW1-1, SW1-2, SW1-3 (B1, B2, B3)
"ON" : Steady signal to corresponding alarm bell output.
"OFF": Pulsed signal to corresponding alarm bell output.
SW1-4, SW1-5, SW1-6 (R1, R2, R3)
"ON" : Steady signal to the outputs of relays RL1-RL3.
"OFF": Pulsed signal to the outputs of relays RL1-RL3.
SW1-7 (GA)
"ON" : Signal in step with the signal on the GA-input.
"OFF": Pulsing signal
Replacing the board
To replace the ARK-2 follow these steps:
1.
Shut down the central by removing the fuses F3-F6 on the KE-2 rectifier.
WARNING!
The power must be disconnected before the board is removed.
2.
Remove the board and replace it with the new board.
3.
Start up the central by inserting F3+F4 and F5+F6 in that order.