Document no.:
S-4-007.875/E
Prepared: 2002-10-01
BM
Revision:
R5 2004-04-07 BM
©
2002, Consilium Marine AB
Service manual
Appendix C: Fault codes C-9
CS3000
124 SUBLOOP CABLE BREAK
Cause
Remedy
Cable break in sub-loop.
Mend the cable. See
Cable break
at
the end of this chapter.
Missing end-of-line unit.
Connect an end-of-line unit.
125 SHORT
CIRCUIT
Short circuit in detector loop reported by a short circuit isolator. If more than one
short circuit isolator has given a fault message, the short circuit is situated
between them. The detectors between the short circuit isolators will give
messages of the type NO ANSWER (22). One message is always CABLE
BREAK (121), since the loop is broken. The short circuit faults must always be
reset before other faults.
Cause
Remedy
Short circuit on detector loop
See
Short circuit
at the end of this
chapter.
126 SHORT CIRCUIT ON PRIM. SIDE
Cause
Remedy
Short circuit between the positive and
negative terminal on the primary side.
Attend to the problem.
127 SHORT CIRCUIT ON SEC. SIDE
Cause
Remedy
Short circuit between the positive and
negative terminal on the secondary side.
Attend to the problem.
141 EARTH FAULT +
Cause
Remedy
Earth fault between positive terminal and
earth.
See
Earth fault
at the end of this
chapter.
FAULT (141) POWER EARTH FAULT +
Earth fault to plus from the power unit.