IMPORTANT: When the controller is power up only by USB and the USB is disconnected then the
actual statistics is lost.
Note:
Suitable conductor protection shall be provided in accordance with NFPA 70, Article 240.
Note:
Low voltage circuits (35 volts or less) shall be supplied from the engine starting battery or an isolated
secondary circuit.
Power supply fusing
A two-amp fuse should be connected in-line with the battery positive terminal to the controller and modules.
These items should never be connected directly to the starting battery. Fuse value and type depends on number
of connected devices and wire length. Recommended fuse (not fast) type - T2A. Not fast due to internal
capacitors charging during power up.
IMPORTANT: 2 A fuse is calculated without BOUT consumption nor extension modules. Real value
of fuse depends on consumption of binary outputs and modules.
Example:
Maximal consumption of binary outputs can be 22 A
2 x 10 A on high current outputs (for 10 seconds)
2 A on all others binary outputs
4.4.4 Measurement wiring
Use 1.5 mm
2
cables for voltage connection and 2.5 mm
2
for current transformers connection. Adjust
,
Nominal Voltage Ph-N (page 158)
,
Nominal Voltage Ph-Ph (page 159)
,
and
by appropriate setpoints in the Basic Settings group.
IMPORTANT: Risk of personal injury due to electric shock when manipulating voltage terminals
under voltage. Be sure the terminals are not under voltage before touching them.
Do not open the secondary circuit of current transformers when the primary circuit is closed. Open
the primary circuit first.
Current measurement wiring
The number of CT’s is automatically selected based on selected value of setpoint
[3Ph4Wire / High Leg D / 3Ph3Wire / Split Ph / Mono Ph].
Generator currents and power measurement is suppressed if current level is bellow <1% of CT range.
To ensure proper function:
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...