InteliLite Global Guide
546
LAI: O
Related FW
1.2.1
Related applications
AMF, MRS
Comm object
9
Description
Logical analog input designed for oil pressure value received from analog sensor. For more information about
wiring of analog inputs
. Limits for this protection are adjusted by setpoints
and
. Delay is adjusted by setpoint
.
Monitoring
Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl
Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
Wrn
Analog value is used for warning protection only.
Wrn + Sd
Analog value is used for warning and Sd protection.
Sd
Analog value is used for Sd protection.
Protection types
Note:
This parameter has to be adjusted via LiteEdit2015.
Under limit
Alarm is activated when value of analog input is under adjusted limits
Over limit
Alarm is activated when value of analog input is over adjusted limits
Under limit + fls
Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls
Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Alarm
Example:
Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be act
Sensor fail alarm will be activated.
Note:
This parameter has to be adjusted via LiteEdit2015.
Note:
This analog function can by also configured on binary input as binary function. In this case chose
binary input in the list of binary inputs. Delay of this binary input is adjusted
via the same setpoint like for analog function.
IMPORTANT: Value from analog input has higher priority than value from ECU.
Oil Pressure
back to Logical analog inputs alphabetically
8.1.6 PLC
List of PLC groups
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...