InteliLite Global Guide
584
Shutdown
Alarm Type
Shutdown
Alarmlist message
Emergency Stop
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
Alarm is activated when binary input
is activated.
The gen-set shuts down in the moment the input is activated and starting is
blocked until the input is deactivated and fault reset is pressed.
Note:
Use red emergency button placed on the switchboard door and connect
it to a binary input of the controller. Then configure the function Emergency
Stop to this binary input. It is recommended to use NC contact of the button.
Note:
The MCB control is not affected by this alarm.
Emergency Stop
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Battery Flat
Alarm evaluated
During cranking
Related applications
AMF, MRS
Description
This alarm will be issued if the controller was reset during cranking of the gen-set.
If this situation occurs, the controller supposes the starting battery is so exhausted
that its voltage drops so low when starter motor is energized that it causes
controller reset.
Sd Battery Flat
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Coolant Temp
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm indicates that the coolant temperature is higher than the temperature set
in
Coolant Temperature Sd (page 179)
setpoint.
Sd Coolant Temp
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Current Unbalance
Alarm evaluated
All the time
Sd Current Unbalance
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...