InteliLite Global Guide
134
3000 .. 3999
Setpoints
Read/Write
Holding Registers
Read: 03, 04
Write: 06, 16
4200 .. 7167
Reserved
registers
Read/Write, depends on
each specific register
Input Registers
Holding Registers
Read: 03, 04
Write: 06, 16
Mapping data types to registers
As there are multiple data types in the controller but only one data type in MODBUS (the register, which is 2
byte long), a mapping table is necessary to compose and decompose the MODBUS messages correctly.
Data type
Meaning
Number of
registers
Data maping
Integer8
1-byte signed integer
1
MSB = sign extension
LSB = value
Unsigned8
1-byte unsigned integer
1
MSB = 0
LSB = value
Integer16
2-byte signed integer
1
MSB = value, MSB
LSB = value, LSB
Unsigned16
2-byte unsigned integer
1
MSB = value, MSB
LSB = value, LSB
Integer32
4-byte signed integer
2
MSB1 = value, byte 3 (MSB)
LSB1 = value, byte 2
MSB2 = value, byte 1
LSB2 = value, byte 0 (LSB)
Unsigned32 4-byte unsigned integer
2
MSB1 = value, byte 3 (MSB)
LSB1 = value, byte 2
MSB2 = value, byte 1
LSB2 = value, byte 0 (LSB)
Binary8
8-bit binary value
1
MSB = 0
LSB = value, bits 0-7
Binary16
16-bit binary value
1
MSB = value, bits 8-15
LSB = value, bits 0-7
Binary32
32-bit binary value
2
MSB1 = value, bits 24-31
LSB1 = value, bits 16-23
MSB2 = value, bits 8-15
LSB2 = value, bits 0-7
Char
1-byte ASCII character
1
MSB = 0
LSB = ASCII value of the character
StrList
Index into a list of strings
1
MSB = 0
LSB = index into the list
ShortStr
Zero-terminated string of
8
MSB1 = ASCII value of the 1. character
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...